PS-05 Protection from fire and smoke
Protect buildings against fire and smoke with fire sections rated at least ninety minutes, early detection with automatic voltage release, an extinguishing or oxygen reduction system, alarm transmission to the local fire brigade, plus recurring fire inspections and drills.
Source: BSI C5 (121-criteria catalogue), PS-05. The statement above is our statement of the clause, read from the published text and cited so you can check it against the official text, not the instrument verbatim. Open BSI C5 (121-criteria catalogue) in the compliance library.
The edition of the catalogue is not stamped here; check the edition your attestation is issued against.
These are the artefacts auditors commonly ask for on this requirement, our guidance rather than text from the standard. Your assessor decides what is sufficient in your context, and asks for samples across the period when a report covers one.
system holds itEvidence a system already holds
none for this control
periodic reviewEvidence produced at each review
- Commissioning certificate for the extinguishing or oxygen reduction installation · Physical access / facilities
- Transmission test record confirming alarm receipt by the local fire service · Physical access / facilities
- Attendance list and debrief notes from the most recent fire drill · Physical access / facilities
governing documentDocuments that govern the control
- Fire compartment plan with the certified resistance rating of each barrier · Policy repository / GRC workspace
First move
Common gaps auditors find
- Cable and pipe penetrations through rated walls left unsealed after works
- Detection zones so coarse that one alert would shut power to an entire hall
- Extinguishing agent inspection overdue against the manufacturer interval
- Drills run for office staff only and never for data centre operations shifts